Yeh tool saath chalne wale appliances se initial UPS VA target aur battery-bank estimate nikalta hai. Result ke teen alag hisay parhein: running watts, planning VA aur idealised battery energy. Exact UPS/battery purchase ke liye model-specific ratings separately match karein.
Apne measured watts kaise enter karein
Default categories ki wattages illustrative fixed presets hain. Agar apne appliances ki measured total input power maloom ho, preset counts zero karein aur total “Koi aur load” mein daalein. Us mode mein extra load continuous assume hota hai: motor starting demand ya fridge cycling automatically measure nahi hoti. Default appliance aur usi appliance ke measured extra watts dono add na karein.
VA target aur actual output watts alag check karein
Model running watts ÷ 0.8 × 1.25 se planning VA nikal kar configured size list mein round up karta hai. 0.8 assumed load power factor hai aur 25% planning allowance. UPS ki output W aur VA dono nameplate limits pass honi chahiye. Is margin mein motor startup surge ki certification included nahi.
Default result khud verify karein
| Step | Default arithmetic |
|---|---|
| Running load | 4×80 + 6×10 + 80 + 200 = 660W |
| Energy average | 320 + 60 + 80 + (200×50%) = 560W |
| Unrounded VA target | 660 ÷ 0.8 × 1.25 = 1031.25VA |
| Configured size selection | 1200VA planning class |
| 4h battery example | 560×4 ÷ (0.85×0.50×24) = 219.61Ah |
220Ah rounded requirement par illustrative 200Ah units ki do parallel strings, har string mein do 12V units, count 4 banati hain. Yeh arithmetic compatible wiring recommendation nahi. Battery age, discharge-rate capacity, temperature, inverter idle draw, cutoff aur current capability ka complete engineering model included nahi.
Battery chemistry aur nominal voltage
Lead-acid 50%, lithium 80% usable fraction aur 85% inverter efficiency selected assumptions hain. Form in factors ko live measured values nahi banata. Lithium ka exact nominal voltage 12.8V/25.6V/51.2V ya doosra ho sakta hai: 12/24/48V planning setting se result different ho sakta hai. Actual rated Wh, approved usable energy aur BMS limits se comparison karein.
Kaunsa result is tool se nahi milta?
- Motor/compressor ka startup surge aur surge duration.
- Exact model ka warranted backup ya capacity-test certificate.
- Charger ka full-charge time, absorption/CV finish aur recharge window.
- Approved series/parallel configuration, cable/protection design ya BMS compatibility.
Result ko model specifications se compare karein
2000VA UPS ki W/VA comparison guide actual output limits ka worked example deti hai. Battery capacity comparison nominal voltage, Ah aur ideal energy ka farq samjhati hai. Charging-time guide recharge ko backup se alag calculate karti hai.
Technical references: Schneider Electric: W/VA limits aur Victron: battery capacity aur discharge rate. Upar examples hamare disclosed inputs ka arithmetic hain, kisi manufacturer ka runtime test nahi.