Solar Battery, Inverter & UPS Load Calculator — Apna Backup Size Maloom Karein

Aap ka result
—

Rates ka source: Aam ghar-elu appliances ke mayari watt andazay aur mayari sizing usool: VA = W ÷ PF × headroom, battery Wh = W × h ÷ (efficiency × depth of discharge) — tamam values editable hain · Laago date: 2026-10-29

Is calculator ko apni website pr lagayen — bilkul free

Neeche wala code copy kr ke apni website ya blog me paste karen — ye calculator wahan hi chal parega. Calculator ke neeche Calculators33 ka chhota sa link ata hai. Height (560) apni site ke hisab se badal sakte hain.

Yeh tool saath chalne wale appliances se initial UPS VA target aur battery-bank estimate nikalta hai. Result ke teen alag hisay parhein: running watts, planning VA aur idealised battery energy. Exact UPS/battery purchase ke liye model-specific ratings separately match karein.

Apne measured watts kaise enter karein

Default categories ki wattages illustrative fixed presets hain. Agar apne appliances ki measured total input power maloom ho, preset counts zero karein aur total “Koi aur load” mein daalein. Us mode mein extra load continuous assume hota hai: motor starting demand ya fridge cycling automatically measure nahi hoti. Default appliance aur usi appliance ke measured extra watts dono add na karein.

VA target aur actual output watts alag check karein

Model running watts ÷ 0.8 × 1.25 se planning VA nikal kar configured size list mein round up karta hai. 0.8 assumed load power factor hai aur 25% planning allowance. UPS ki output W aur VA dono nameplate limits pass honi chahiye. Is margin mein motor startup surge ki certification included nahi.

Default result khud verify karein

StepDefault arithmetic
Running load4×80 + 6×10 + 80 + 200 = 660W
Energy average320 + 60 + 80 + (200×50%) = 560W
Unrounded VA target660 ÷ 0.8 × 1.25 = 1031.25VA
Configured size selection1200VA planning class
4h battery example560×4 ÷ (0.85×0.50×24) = 219.61Ah

220Ah rounded requirement par illustrative 200Ah units ki do parallel strings, har string mein do 12V units, count 4 banati hain. Yeh arithmetic compatible wiring recommendation nahi. Battery age, discharge-rate capacity, temperature, inverter idle draw, cutoff aur current capability ka complete engineering model included nahi.

Battery chemistry aur nominal voltage

Lead-acid 50%, lithium 80% usable fraction aur 85% inverter efficiency selected assumptions hain. Form in factors ko live measured values nahi banata. Lithium ka exact nominal voltage 12.8V/25.6V/51.2V ya doosra ho sakta hai: 12/24/48V planning setting se result different ho sakta hai. Actual rated Wh, approved usable energy aur BMS limits se comparison karein.

Kaunsa result is tool se nahi milta?

  • Motor/compressor ka startup surge aur surge duration.
  • Exact model ka warranted backup ya capacity-test certificate.
  • Charger ka full-charge time, absorption/CV finish aur recharge window.
  • Approved series/parallel configuration, cable/protection design ya BMS compatibility.

Result ko model specifications se compare karein

2000VA UPS ki W/VA comparison guide actual output limits ka worked example deti hai. Battery capacity comparison nominal voltage, Ah aur ideal energy ka farq samjhati hai. Charging-time guide recharge ko backup se alag calculate karti hai.

Technical references: Schneider Electric: W/VA limits aur Victron: battery capacity aur discharge rate. Upar examples hamare disclosed inputs ka arithmetic hain, kisi manufacturer ka runtime test nahi.

Aap ke sawal

Common questions

Apne ghar ke liye inverter ka size kaisay maloom karoon?
Un tamam cheezon ke watts jama karein jo aik sath chalni hain, power factor (0.8) se taqseem karke VA nikalein, phir motor start ke liye taqreeban 25% izafi gunjaish shamil karein — tool ye sab karke standard inverter size tak round kar deta hai.
4 ghantay backup ke liye kitni batteries chahiye hongi?
Ye load par depend karta hai: battery Wh = load watts × ghantay ÷ (inverter efficiency × usable depth of discharge). 4 ghanton ke 660 W zaroori load ke liye lead-acid par 24 V par taqreeban 220 Ah chahiye — yani taqreeban chaar 200 Ah batteries.
Lithium battery bank chhota kyun nikalta hai?
Lithium ko nuqsan ke baghair taqreeban 80% tak discharge kiya ja sakta hai, jabke lead-acid ko sirf taqreeban 50% tak istimal karna chahiye — is liye utne hi backup ke liye lithium bank chhota chahiye hota hai (lekin per Ah qeemat zyada hoti hai).
Kya fridge ko puray watts par ginna chahiye?
Inverter size ke liye ji haan (compressor ko start bhi hona hai aur chalna bhi hai), lekin battery energy ke liye tool fridge aur freezer ko 50% duty-cycle par rakhta hai, kyunke compressor taqreeban aadha waqt band rehta hai.