1000W constant load ke liye 200Ah battery ka runtime us ke voltage aur usable energy par depend karta hai. Illustrative 12V, 200Ah lead-acid bank, 50% usable fraction aur 85% efficiency se 1.02 ghantay nikalte hain. Yeh ideal planning estimate hai, battery ka guaranteed ya measured backup nahi.

Ek hi Ah par voltage ka asar
| Bank example | Assumed usable AC energy | 1000W par ideal hours |
|---|---|---|
| 12V 200Ah, 50% usable, 85% efficiency | 1020Wh | 1.02h |
| 24V 200Ah, same assumptions | 2040Wh | 2.04h |
| 12.8V 200Ah, illustrative 80% usable, 85% efficiency | 1740.8Wh | 1.74h |
Formula V × Ah × usable fraction × efficiency ÷ load W hai. 24V 200Ah bank mein nominal energy 12V 200Ah se double hai: yeh sirf voltage ka free efficiency gain nahi, total stored-energy difference hai. Lithium example ka voltage 12.8V hai, har pack ka nominal voltage label se lein.
12V par battery current kyun important hai?
Illustrative DC current = 1000 ÷ (battery V × inverter efficiency). 12V aur 85% par 98.04A, 24V aur same efficiency par 49.02A. Yeh fixed actual readings nahi: voltage girne ya efficiency badalne se current badalta hai. Battery/BMS current rating, inverter DC specification, protection aur conductor design separately required hain.
Lead-acid ki 200Ah label rating ka scope
Rated Ah ek specified discharge test condition par hota hai. Manufacturer ki Peukert explanation rate badhne par available capacity ka farq samjhati hai. Is liye high-current 1000W use mein simple Wh model optimistic ho sakta hai. Exact correction ke liye apne battery model ki discharge tables aur cutoff conditions chahiye.
1000W load ke liye kitne VA?
Assumed load PF 0.8 ho to 1000 ÷ 0.8 = 1250VA. Illustrative 25% allowance ke saath targets 1250W aur 1562.5VA hain. Yeh 1600VA ya 2000VA ke har UPS ki compatibility guarantee nahi: output W/VA dono ratings, motor startup aur surge duration verify karein. W aur VA ki manufacturer explanation dono limits check karne ki wajah batati hai.
Load half karne ka matlab
Ideal 1020Wh model 1000W par 1.02h aur 500W par 2.04h deta hai. Real battery mein efficiency, discharge-rate effect aur idle consumption badal sakte hain, is liye measured runtime exact double hona zaroori nahi.
Apne case ka useful record
- Battery nominal voltage, Ah/Wh, chemistry aur model.
- Starting SOC, health aur rated discharge conditions.
- Measured simultaneous AC load aur startup demand.
- Manufacturer usable fraction/current limits aur inverter cutoff.
UPS load calculator se initial bank-size scenario compare karein. Calculator ka output measured capacity test ya installation design nahi.